Product Description
Description
Primary Current Injection Test Sets are used to loading, Calibration, and testing of CT bimetals relays, Protection relays etc. Mostly Primary Injection Test set is designed as per customer specification. The Primary Injections Test sets are of 15 minutes ON/30Minutes OFF duty i.e. testing duty only. Loading transformers are designed for continuous use for Temperature Rise or bus duct/Bus Bar etc. Optional accessories requirement may include cable termination, timer, Temperature Indicator, multiple contractors, individual Phase control etc. Equipment is Compact in nature. It is available in portable trolley type/stationery type model And Optional digital/analog timer. Main Transformer up to 25,000Amps.
Features
Electronic Parameter Monitoring.
Multiple safety interlocks for the operator.
Rugged in construction for site application.
Detailed Technical Specifications
Three Phase Primary Current Injection Test Set | ||
Sr. No. | Parameters | Description |
1 | I/p Voltage | 380/ 400V Three Phase 50/ 60HZ AC Supply |
2 | O/p Current | Up to 25000A |
3 | Capacity | Up to 500KVA |
4 | Duty Cycle | Intermittent or continuous |
5 | Control | 1- The unit can be manual/motorized control for current variation and push-button controlled. 2- The unit can be microprocessor based complete with the onboard digitized panel. 3- The unit can be PLC based complete with a computer, HMI memory, printer etc. for operation. |
6 | Power Components | 1- Step down transformer : 3 Nos. double wound transformer shall be used for supplying high Current and low voltage for testing. 2 - Auto Transformer : 3 Nos. Motorized Auto Transformer shall be used for controlling the output voltage from zero to maximum to control the load Current. |
7 | Metering | 1- Ampere meter : 3 Nos. Digital Ampremeter shall be provided with 0.5 classes CT to indicate the output current. The size of the amperemeter shall be 96 sq.mm. 2 - Voltmeter: A digital voltmeter with selector switch shall be provided to indicate the output voltage each phase/phase to phase, if required. 3 - Line On Indicator: Neon lamp indicators are provided for input indication. 4- Main ON/OFF switch: Three poles ON/OFF is provided for input ON &OFF. |
8 | Termination | An output is brought on Copper bus-bars |
9 | Control Panel | (i) ON/OFF switch (ii) Separate indication lamps for all three phases in the three-phase unit. (iii) Digital Output Ampere meter and Voltmeter with selector switch. (iv) Push buttons for raising and lowering the Output current separately for each phase with change over switch and Push buttons for raising current of all the phases simultaneously |
10 | Regulating Transformer |
Will be suitable for Motorized operation having limit switches, lifting arrangement for Regulating Transformer and for the whole unit, Input & Output Indicators. The whole unit will be fitted with suitable input 3 Phase 4 Wire and will be mounted on 6inch caster wheels. Will be suitable for Motorized or manual operation having limit switches. |
11 | Step Down Transformer | Shall be air cooled type. Primary winding having DCC insulation and the secondary winding of bare copper strip (RYB & Neutral). The unit shall be housed in an MS Sheet body supported an angle iron frame. Output RYB-N shall be brought out on the Copper bus bar of electrolyte grade. The output with a connected star so in case of need, each phase can be used independently. Casted wheels shall be of 6 inch dia for easy movement. |
![]() |